Digital time switch with yearly and astronomical time program.
Function description
- 1 channel
- External input
- Connectable sensors (external selector switch, sequence timer)
- Connectable switches (ON or OFF permanent switching)
- DuoFix spring terminals
- For 2 conductors each
- Wire or strand (with or without wire end sleeve)
- Wire diameter: 0.5 - 2.5 mm²
- Button for releasing plug-in connection
- Text-oriented user guidance in display
- Preset date and time
- Fully operable without mains connection
- 800 memory locations
- Interface for OBELISK top2 memory card (PC programming)
- 2 insertable switching programs
- Copying programs
- Storing programs
- 8 year power reserve (lithium battery)
- Zero-cross switching for levy-saving switching and high lamp loads (not with 24 V devices)
- Automatic summer / winter time changeover
- Can be deactivated
- Date rule options are already stored for Europe, the USA and other countries
- own date rule options or changeover around set dates are available
- ON-OFF switching times
- Pulse program
- Cycle program
- Extensive yearly clock functions
- Basic weekly program and 14 different weekly programs with priority levels and date ranges
- Permanent ON / permanent OFF with highest priority via date range program option
- Fixed and variable public holidays, public holidays dependent on Easter, day and date ranges with serial pattern
- Public holiday database for Germany including all Federal states, Switzerland, France etc.
- Program simulation on clock display
- Graphic program simulation with 12 month overview for all channels on PC
- Astronomical time switch function (automatic calculation of sunrise and sunset times for the whole year)
- Offset for adjusting of sunrise and sunset times
- Position data via coordinates or country / city lists can be programmed
- Optional production of own city list (favourites) and a table with own astronomical times on PC
- Fixed ON-OFF switching times can be programmed (e.g. night time interruption)
- Simulation of astronomical switching times (calculated astronomical times and programmed ON / OFF switching times) for the whole year
- Various astronomical setting options (evening ON - mornings OFF or evenings OFF - mornings ON, astronomical pulse)
- Switching preselection
- Permanent switching ON / OFF
- Count-down timer
- Integrated operating hour counter
- Reset option
- Service function for monitoring maintenance intervals
- Holiday program
- 2 random programs
- Display back light (can be turned off)
- PIN coding
Technical data |
Operating voltage | 110 – 240 V AC |
Frequency | 50 – 60 Hz |
Width | 3 modules |
Installation type | DIN rail |
Type of contact | Changeover contact |
Switching output | Phase-independent |
Opening width | < 3 mm |
Program | Yearly program, Astronomical program |
Program functions | ON-OFF, Pulse, Cycle |
Number of channels | 1 |
External inputs | 1 |
Number of memory locations | 800 |
Power reserve | 8 years |
Switching capacity at 250 V AC, cos φ = 1 | 16 A |
Switching capacity at 250 V AC, cos φ = 0,6 | 10 A |
Incandescent/halogen lamp load | 2600 W |
Incandescent/halogen lamp load 120 V | 1300 W |
Energy saving lamps | 37 x 7 W, 30 x 11 W, 26 x 15 W, 26 x 20 W, 11 x 23 W |
Energy saving lamps 120 V | 18 x 7 W, 15 x 11 W, 13 x 15 W, 13 x 20 W, 11 x 23 W |
LED lamp < 2 W | 50 W |
LED lamp 2-8 W | 180 W |
LED lamp > 8 W | 200 W |
Switching capacity min. | ca. 10 mA |
Shortest switching times | 1 s |
Time accuracy at 25 °C | ≤ ± 0.5 s/day (quartz) |
Time basis | Quartz |
Stand-by consumption | ~0.6 W |
Capacity loss max. | 1.1 W |
Memory card supplied | No |
Type of connection | DuoFix spring terminals |
Display | LCD |
Keyboards | 4 touch buttons |
Housing and insulation material | High-temperature resistant, self-extinguishing thermoplastic |
Type of protection | IP 20 |
Protection class | II according to EN 60 730-1 |
Voltage | 110-240 V AC |
Ambient temperature | -30°C ... 45°C |
Price includes GST